| Items |
Descriptions |
| Input |
Power input |
Recommend Voc range: 220V: 360~450Vdc; 380V: 550~900Vdc
Recommend Vmp range: 220V: 250~350Vdc. 380V: 450~900Vdc
Max DC input: 450Vdc(220v class), 380V 900Vdc(380v class) |
AC 1PH, 220V(-15%) ~ 240V(+10%)
AC 3PH, 380V(-15%) ~ 440V(+10%) |
| Allowable range |
Voltage fluctuating range: -15%~10%; voltage unbalance <3%;
frequency: 47Hz~63Hz |
| Output |
Output voltage |
0V~input voltage, tolerance<5% |
| Output frequency range |
0.1 -500.0Hz |
| Performance |
Overload capacity |
150% of rated current: 60s, 180% of rated current: 3s, 190% of rated current: 0.5s |
| Frequency resolution |
Digital setting: 0.01Hz
Analog setting: Max. frequency*0.025% |
| Carrier frequency |
0.8 ~ 16 kHz, can be automatically adjusted according to load characteristics |
| Input/output |
Analog input AI |
<=22kW: 1 channel AI: 0/4~20mA, 0-10V, >=30kW 2 channels |
| Analog output AO |
<=22kW: 1 channel AO: 0/4~20mA, 0-10V, >=30kW 2 channels |
| Digital input |
<=22kW: 4DI, >=30kW: 8DI |
| Digital output |
<=22kW: 1 DO, >=30kW: 2DO
<=22kW: 1 RO, >=30kW: 2RO 3A/AC250V, 1A/DC30V |
| PFI / PFO |
1 channel pulse frequency input and output |
| Communication |
Built-in RS485 interface with Modbus RTU |
| Control functions |
Motor control mode |
VF control, Sensor-less vector control |
| Run command channel |
Operation panel setting, control terminal setting, communication setting |
| Frequency setting channel |
Operation panel, communication, UP/DOWN regulated value, AI, PID, multi-step speed, PFI |
| DC braking |
Braking time: 0.0s~60.0s, braking current: 0.0%~100.0% of rated current |
| Jog |
Jogging frequency range: 0.00Hz~Maximum frequency |
| AVR |
Automatic voltage regulation |
| Automatic carrier frequency |
Automatically regulate carrier frequency according to load characteristic |
| Environment |
Protection |
Over-current, over-voltage, under-voltage, phase loss, output interphase short circuit, overheat,
motor overload, external failure, lost connection of analog input, stall prevention, etc. |
| Altitude |
With altitude below 1000m, derate >1000m |
| Operating |
-10~+50℃, derate >40℃ / 20~95%RH, without condensation water drop |
| Storage temperature |
-20~+60℃ |
| Vibration |
<5.9m/s2 (0.6g) |
| Structure |
Degree of protection |
IP20/IP00 |
| Cooling mode |
Force-air cooling |