- Home > Products > Electric Drive > Medium Voltage Drives > SBH Series Medium Voltage Drive
SBH Series Medium Voltage Drive
-
● 4th generation MV drive for general purpose
● 3, 3.3, 6, 6.6, 10, 11kV voltage class
● VF, VF+PG, SVC, closed-loop Vector Control
● Power unit bypass and phase shift technology protection
● 2 drive 1 motor with thermal redundancy technology
● Hot redundancy technology
● 3-full (full load, full voltage, full current) testing
Specifications
- Specifications
- Downloads
Specifications
|
|
Items |
Descriptions |
|
Input |
Rated voltage, frequency |
3 phase: 3-11kV, 50Hz/60Hz |
|
Allowable range |
Voltage fluctuating range: -20%~15%; voltage unbalance: <3%; frequency: 50/60 ±10% |
|
|
Output |
Output voltage |
Three-phase, 0V~input voltage, tolerance<5% |
|
Output frequency range |
0.00 - 120.00Hz |
|
|
Output power range: |
160-30,000 kW, customized for larger power rating |
|
|
Performance |
Overload capacity |
120% of rated current for 120s |
|
Frequency resolution |
Digital setting: 0.01Hz; |
|
|
Harmonic |
<=2%, meet IEEE519 |
|
|
Technology |
Voltage-source inverter(VSI) |
|
|
Rectifier |
10kV: 48 pulses rectifier, 6kV: 30 pulses rectifier, customize for customer |
|
|
Input voltage drop without reset |
25% |
|
|
Power factor |
>=0.96 |
|
|
Efficiency (Inverter) |
>=98% |
|
|
Total efficiency |
>=96.5% |
|
|
Power cells |
8pcs/phase for 10kv, 9pcs/phase for 11kV. Customized for customer 5pcs/phase for 6kV, 6pcs/phase for 6.6kV, Customized for customer Support mechanical and electrical bypass Electrical and mechanical bypass, optional neutral phase shift bypass |
|
|
Certification |
CE, EAC |
|
|
Output voltage level |
Phase voltage level: 2n+1, line voltage level: 4n+1, n= power cell quantity of each phase |
|
|
Shutdown time upon power loss |
>=300ms |
|
|
Output voltage spike rate |
<1,000v/μs |
|
|
Input/output |
Analog input AI |
3 channels AI: 0/4~20mA, 0-10V |
|
Analog output AO |
4 channels AO: 0/4~20mA, 0-10V |
|
|
Digital input |
14 digital input |
|
|
Digital output |
10 relay output |
|
|
Communication |
Built-in RS485 interface with Modbus RTU, optional for ProfibusDP, Profinet,Bluetooth, USB port, Ethernet |
|
|
Control |
Motor control mode |
VF, VF+PG, SVC, VC+PG |
|
Run command channel |
HMI, control terminal setting, communication setting, PLC, DCS, .etc |
|
|
Frequency setting channel |
HMI, communication, UP/DOWN regulated value, AI, PID, multi-step speed, logic |
|
|
Control power |
1phase 220V, 3kVA, 50/60Hz |
|
|
Acceleration & deceleration |
Linear, S curve ACC/DEC, 0.1-3600 sec |
|
|
Jog |
Jogging frequency range: 0.10Hz~50.00Hz |
|
|
AVR |
Automatic voltage regulation |
|
|
Automatic carrier frequency |
Automatically regulate carrier frequency according to load characteristic and environment temperature |
|
|
Master-Slave |
Optional power balance cabinet |
|
|
Multistep speed method |
32 steps |
|
|
Functions |
Integrated PID, Speed search start, Flying Restart, Load profile, Output power meter, Integrated energy consumption optimization meter, Power loss ride through 2 sets PLC models, |
|
|
Optional |
Bypass cabinet, manually and automatically, |
|
|
Others |
Tracking start, stall prevention, oscillation suppression, accurate dead zone compensation functions |
|
|
Environment |
Protection |
Over-current, over-voltage, under-voltage, phase loss, output interphase short circuit, overheat, |
|
Altitude |
With altitude below 1000m, derate >1000m |
|
|
Operating |
-10~+40℃ / <95%RH, without condensation water drop |
|
|
Storage temperature |
-40~+70℃ |
|
|
Vibration |
<5.9m/s2 (0.6g) |
|
|
Structure |
Degree of protection |
IP20, IP30, IP31, IP41, IP42, IP54 customizable |
|
Bypass cabinet |
Manual and Auto operation mode Rate voltage 7.2/12kV Rate current: Refer to MVD rated specification Shor-time withstand current for 1s 4kA/1s Mechanical life operation 500,000 times, optional 1,000,000 times Opening time ≤30ms Closing time ≤90ms |
|
|
Maintenance |
Single side/double side |
|
|
Power cable input |
Bottom input, bottom output, optional for other | |
|
Temporary lost time |
8 ms |
|
|
Distance from MVD to motor |
>500m |
|
|
Transformer |
Copper/Aluminum, H insulation, with temperature sensor |
|
|
Noise |
<75 dB at 1m distance |
|
|
Cloud service |
Provide cloud service, easy monitoring and remote support |
|
Cooling mode
|
Forced-air cooling, liquid cooling, air-liquid cooling |
|
|
HMI |
Language |
7" English/Chinese, optional other size |
Downloads
| File Name | Type | Language | File Type | Update | Download |
|---|---|---|---|---|---|
| SBH MV Drive _EN-V3.2 | Catalog | English | 2025-06-09 | 4.71MB | |
| SBH H4 Integrated user manual_EN_V4 | Manual | English | 2025-06-09 | 4.96MB | |
| SBH H3.5 Standard user manual_EN_V4 | Manual | English | 2025-06-09 | 4.85MB | |
| SBH H3.5 Standard user manual_EN_V4 | Manual | English | 2025-06-09 | 4.85MB | |
| SBH H4 Integrated user manual_EN_V4 | Manual | English | 2025-06-09 | 4.96MB | |
| SBH Flyer_EN_V1.0 | Catalog | English | 2025-06-09 | 3.7MB | |
| SBH MV Drive _EN-V3.2 | Catalog | English | 2025-06-09 | 4.71MB |
English
中文